General Procedure for Paralleling Generators in Electrical Machines uploaded by Gust M uploaded in Engineering Study material at lecturenotes.net
General Procedure for Paralleling Generators:
Consider the figure shown
below. Suppose that generator G2 is to be connected to the running system as
shown below:
Using Voltmeters, the field current of the oncoming generator should
be adjusted until its terminal voltage is equal to the line voltage of the
running system.
Check and verify phase sequence to be identical to the system phase
sequence. There are 2 methods to do
this:
One way is using the 3 lamp
method, where the lamps are stretched across the open terminals of the switch
connecting the generator to the system (as shown in the figure below). As the
phase changes between the 2 systems, the lamps first get bright (large phase
difference) and then get dim (small phase difference). If all 3 lamps get
bright and dark together, then the systems have the same phase sequence. If the
lamps brighten in succession, then the systems have the opposite
phase sequence, and one of the sequences must be
reversed.
Using a Synchroscope – a meter that measures the
difference in phase angles (it does not check phase sequences only phase
angles).
Check and verify generator frequency is same as that of the system
frequency. This is done by watching a frequency of brightening and dimming of
the lamps until the frequencies are close by making them to change very
slowly.
Once the frequencies are nearly equal, the voltages in the 2 systems will change phase with respect to each other very slowly. The phase changes are observed, and when the phase angles are equal, the switch connecting the 2 systems is closed.
--
Write a public review