An external
fault in the star side will result in current flowing in the line current transformer of the affected phase and at the same time a
balancing current flows in the neutral current transformer, hence the resultant
current in the relay is therefore zero. So this REF relay will not be actuated
for external earth fault. But during internal fault the neutral current
transformer only carries the unbalance fault current and operation of Restricted Earth Fault
Relay takes place. This scheme of restricted
earth fault protection is very sensitive for internal earth
fault of electrical power transformer. The protection scheme is comparatively
cheaper than differential protection scheme.
Restricted
earth fault protection is
provided in electrical power transformer for sensing internal earth fault of
the transformer. In this scheme the CT secondary of each phase of electrical
power transformer are connected together as shown in the figure. Then common
terminals are connected to the secondary of a Neutral Cu rent Transformer or
NCT
The
CT or Current Transformer connected to the neutral of power transformer is
called Neutral Current Transformer or Neutral CT or simply NCT. Whenever there
is an unbalancing in between three phases of the power transformer, a resultant
unbalance current flow through the close path connected to the common terminals
of the CT secondaries. An unbalance current will also flow through the neutral
of power transformer and hence there will be a secondary current in Neutral CT
because of this unbalance neutral current. In Restricted Earth Fault scheme the common
terminals of phase CTs are connected to the secondary of Neutral CT in such a
manner that secondary unbalance current of phase CTs and the secondary current
of Neutral CT will oppose each other. If these both currents are equal in
amplitude there will not be any resultant current circulate through the said
close path. The Restricted
Earth Fault Relay is connected in this close path. Hence the
relay will not response even there is an unbalancing in phase current of the
power transformer.